Professionals & PartnersElectricity & GridsRipple control
Ripple control: convert systems by the end of 2029
BKW will decommission the ripple control system on 31 December 2029. Systems currently controlled by it must be professionally disconnected by this date. Here, as a specialist partner, you can find out what measures are necessary and how to proceed.
The essentials
What does the shutdown mean for you?
For around 50 years, the ripple control system has controlled boilers, electric heating systems, heat pumps and other installations. It is now reaching the end of its technical service life.
As an electrical installer, you play an important role in the transition: you professionally disconnect the affected systems from the ripple control system and work with the owners to ensure that the systems continue to function perfectly.
Shutdown on 31 December 2029Disconnection takes place on the system side, not at the ripple control receiver.Completed work must be reported to BKW
How we inform affected customers
From mid-November 2026, we will inform the owners of affected installations personally by letter about the shutdown of the ripple control system.
We explain the impact of the shutdown and what measures are required. In doing so, we point out that you must commission an electrical installer in good time to carry out the necessary work. It is important to us that the affected systems continue to function properly. We are therefore informing you and the affected owners at an early stage about the necessary procedure and are happy to answer any questions you may have.
Affected systems
Which measures are required for which installation?
Depending on the system type, the next steps after disconnection from ripple control will differ. Select the relevant system type to see the recommendations. Disconnection is always carried out on the system side, not at the ripple control receiver (RCR).
Man in an orange jacket in front of a coastal landscape with rocks and the sea in the background
Electric water heaterAfter separation, suitable control must be implemented. We recommend intelligent, flexible control, for example via an energy management system. Alternatively, a timer or control via the built-in thermostat may be considered.
BKW assessmentImportant to knowTimer switchIf control via EMS or other intelligent and flexible control systems is not implemented, we recommend control via timer switch as the next best alternative. We recommend setting the timer switch so that the system is switched on between 22:00 and 04:00. The switch-on times should be distributed as evenly as possible across this period and within the individual hours. This can, for example, prevent many systems from being switched on on the hour at the same time. Alternative: thermostat controlControl via the boiler’s own thermostat is possible. In this case, the built-in thermostat controls the hot water preparation and no additional control is required. It should be noted that, with this solution, heat losses and electricity consumption could increase, which may lead to higher electricity costs for customers.By thermostat control, we mean a solution in which the boiler is permanently enabled and the built-in thermostat controls the hot water preparation. If thermostat control is being considered, we therefore recommend that the electrical installer discuss the existing needs together with the owner. The primary aim is to clarify the needs relating to cost-effectiveness, energy efficiency and hot water comfort. 
Why separating from the RSE is necessary
To ensure that affected systems function independently of ripple control after shutdown, they must be completely disconnected from the ripple control receiver (RCR). To do this, the system contactor on the system side must be disconnected from the RCR.
Even if we no longer send control signals, independent control of a system is not fully guaranteed as long as it is connected to the RSE.
Procedure
Successful migration in four steps
Proceed systematically for each affected installation.
01Inspect the installation and define measuresClarify which installation is affected and whether a new control solution or replacement is required after the disconnection. Coordinate the procedure with the owners.02Disconnect installation from ripple controlDisconnect the system contactor from the ripple control receiver (RCR). Disconnection must always be carried out on the system side, not at the RCR.03Ensure functionalityIf necessary, implement the new control solution or support the system replacement. Check whether the system functions properly afterwards.04Report BKW conversionNotify us if no more systems are connected to the relevant ripple control receiver. Please also take into account any second meter. BKW will handle its removal as well as the removal of the RSE.
Report the conversion via ElektroForm
Reporting process
Unregister ripple control receivers and secondary meters
As soon as all systems have been disconnected from the relevant ripple control receiver, please inform BKW.
If a system has been disconnected from a secondary meter, please also notify BKW. In this case, the connected installations must be transferred to another meter.
Report the change via ElektroForm
Additional tariffs
What applies to the additional tariffs UR and SR?
With the shutdown of the ripple control system, the additional tariffs “LV interruptible (UR)” and “LV controllable (SR)” will also be discontinued.
UR tariff (LV interruptible)Heat pumps and direct heating systems with the UR tariff are usually interrupted via ripple control twice a day for two hours each time. In return, the affected customers receive remuneration through the UR tariff.SR tariff (LV controllable)Factory-controlled electric storage heaters with the SR tariff are switched on and off via ripple control. This control is remunerated through the SR tariff.Important: Both additional tariffs cease to apply as soon as the affected system is disconnected from ripple control – but no later than when it is switched off on 31 December 2029. Any second meter must also be deregistered and uninstalled.
Good to know
Framework conditions
Renovation obligationsIn the cantons of Bern, Basel-Landschaft and Solothurn, conventional and utility-controlled electric storage heaters must be replaced by law. In Solothurn by 31 December 2030, and in Bern and Basel-Landschaft by 31 December 2031.FundingThe cantons of Bern, Basel-Landschaft, Solothurn and Jura offer various subsidies that are particularly worth looking into if you are considering replacing a system.Abolition of imputed rental valueThe imputed rental value will be abolished at the end of 2028. Until then, the costs of renovations can be claimed for tax purposes. This may be a reason to carry out renovations, such as replacing a heating system, before the end of 2028.More guidesThe public energy advisory service of the canton can be a suitable point of contact for customers seeking independent, free initial advice.
FAQ
Answers to your questions
Here you will find answers to frequently asked questions about the technical changeover, the notification process and the applicable framework conditions for the deactivation of ripple control.
The costs for all conversions to the affected installations as well as any further adjustments to the building installation shall be borne by the owners.
If customers are unsure whether their system is affected by the shutdown, they can contact us directly.A photo of the electrical panel or the ripple control receiver may be helpful for clarification.Alternatively, customers can contact you directly to have it checked whether their system is affected and what measures are necessary.
Yes, if a system is disconnected from the ripple control receiver, this process must be reported to BKW. A notification form is available for this purpose and must be submitted to BKW. The obligation to notify the grid operator is set out in the works regulations. The notification form confirms that no systems are still connected to the relevant ripple control receiver (RCR) and that the RCR can be deinstalled. The notification process is used to identify the affected systems – and therefore the affected customers. The aim is for all affected systems to be disconnected from ripple control by the shutdown date (31 December 2029). This ensures that the affected customers will not suffer any loss of convenience as a result of the shutdown. The notification process is therefore correspondingly important.
Any secondary meter must be removed if the associated installation is disconnected from the ripple control system, because this meter causes unnecessary additional costs for the customer. Specifically, a secondary meter costs around 90 francs per year, which is reflected in the metering tariff. The secondary meter made it possible to bill an additional tariff (UR or SR tariff). Since any additional tariff no longer applies when the installation is disconnected from the ripple control system (or when the ripple control system is switched off on 31 December 2029), the secondary meter becomes obsolete from that point onwards and causes unnecessary costs.
The installation downstream of the dismantled secondary meter must be reconnected to another meter. For example, if a heat pump that uses the UR tariff is disconnected from the ripple control system, it must be reconnected to another meter.
Yes, provided the timer is disconnected from the general power supply.
Tenants do not need to take any action themselves. Responsibility for the changeover lies with the owners of the affected installations.We will inform tenants who use an installation with an additional tariff – for example a heat pump with a UR tariff or a utility-controlled electric storage heater with an SR tariff – personally by letter by the end of 2026. The reason for this is the statutory obligation to provide information in the event of changes to additional tariffs.Tenants whose installations are not subject to an additional tariff will not receive a personal letter.
Do you have questions about disconnection from ripple control, the notification process or a new control solution? Our connection service will be happy to assist you.

12/500

Send

Please fill in all required fields correctly.

FacebookLinkedInInstagramLegal informationData protectionImprintTranslations on our websitesGTC & legalPrivacy settings